What Have I Learned? - Cascade Control (Part 3)

By Greg McMillan

We conclude with a ten step implementation procedure for helping you get the most out of your cascade control system.

(1) Pick a fast secondary measurement with enough rangeability to correct for nonlinearities and disturbances. Flow is the most popular secondary measurement because it is relatively fast and can compensate for nonlinear valve characteristics and pressure upsets. However differential head meters may lack sufficient rangeability for some applications. A common triple cascade loop is vessel temperature to jacket temperature to makeup coolant flow, which makes the primary loop linear and corrects for coolant makeup temperature and pressure upsets and non-ideal control valve behavior. If you have a positioner on the coolant valve (highly recommended), you have a quadruple cascade. If you have a digital valve controller (DVC) as your positioner with an inner loop of actuator pressure, you have graduated to a quintuple cascade control system.

(2) If you have a positive feedback network for the integral mode in your secondary PID and have fast reliable feedback of the variable that the secondary loop is manipulating, enable external feedback ("Dynamic Reset Limit") in the secondary PID and provide the manipulated variable for external reset feedback. Fieldbus read back is fast enough for any valve with a pneumatic actuator whereas HART read back is fast enough for very large pneumatic actuators. Some variable speed drives (VSD) have tachometer feedback creating an inner speed loop. The use of speed for external reset feedback is particularly useful for dealing with overly conservative maximum ramp rate settings in the VSD.

(3) Remove set point filtering on the secondary loop.

(4) Tune the secondary (inner) loop first for a fast response to set point changes. Consider set point feedforward in the secondary loop for a low secondary PID controller gain (< 0.5) to make the secondary response to setpoint changes faster.

(5) If you a positive feedback network for the integral mode, enable external feedback ("Dynamic Reset Limit") in the primary PID and provide the secondary loop PV for external reset feedback.

(6) Put the secondary loop in the remote setpoint cascade (RCAS) mode.

(7) Make sure the output limits of the primary PID match up with the setpoint limits of the secondary PID.

(8) Add a PV noise filter to the primary loop just large enough keep from unnecessarily moving the secondary loop set point.

(9) Tune the primary (outer) loop for a smooth response. The primary closed loop time constant must be at least five times larger than the secondary closed loop time constant to eliminate any interaction between the primary and secondary loops. If the secondary loop time constant cannot be made faster, you must slow down the primary loop time constant by decreasing the primary controller gain.

(10) Add feedforward signals as necessary to the primary controller output to improve its response to measured disturbances. Add a PV noise filter to the feedforward signal just large enough to prevent unnecessary movement of the secondary loop set point. Add dynamic compensation (delay and/or lead/lag) to the feedforward signal so that the correction by the secondary loop doesn't arrive too soon or too late relative to the disturbance at the same point in the process.



5 Comments

To familiarize yourself in this kind of industrial application , knowing the proper indications of valves in an automation is a wisely action and will positively keep us in track. Thanks for sharing this information.Good Day!

This article is epic, I am going to put this in my bookmarks before I misplace the address, I don't think I'll ever make it back here again otherwise :)

What is Chennai Web Directory about? Chennai Web directory is the only web directory featuring large collection of websites servicing Chennai and Tamil Nadu. They display websites of all categories which helps you to find the details about a product or service without asking your family, friends, neighbors, relatives, etc.

To get listed in online web directory for free, Choose your preferred page by browsing through the different categories and click on the 'get listed free' link. Fill up the form and get listed. You can also go for multiple submissions from 'Get Listed Free' link in the header of every page. Just search with your preferred keyword under preferred category and see a list of pages being displayed. Now, choose the pages matching your website and submit your URL. The last and the easiest option to get listed in OWD is to search with your keyword in the search box and choose the most appropriate page. Give your listing and wait for our editors to approve it. Please don't forget to go through our submission rules before submission.

Do you have to include a link directory on your website in order to have the other sites link to you? No, there are paid options that allows you to get the links without linking back. This is known as 'one-way' linking.


Leave a comment


Subscribe

Archives

The opinions expressed here are the personal opinions of Greg McMillan and Terry Blevins. Content published here is not read or approved by Emerson before it is posted and does not necessarily represent the views and opinions of Emerson. © 2006-2010 Greg McMillan and Terry Blevins. All rights reserved.