One of the simplest and easiest techniques to evaluate and implement is set point feed forward. The maximum feedforward gain is the inverse of the process gain. You just need to make sure the process gain is converted to the same units used for the feedforward gain and only a fraction of the maximum is used as the actual feedforward gain to allow for nonlinearities, errors, and PID action. New adaptive controllers such as DeltaV Insight can find and schedule the process gains and hence the set point feedforward.
If the controller gain is large (> 1.0) and the controller structure has proportional action on error, set point feed forward has little value because there is already a sizeable step in controller output from a set point change. However, large dead times can cause low controller gains. Here, set point feedforward can get you to a set point much faster, which can be useful for loop set points driven by batch, cascade, or advanced control.

Thanks a lot! That was very helpful, I just Dugg your website.
I just found this blog a while back when a buddy recommended it to me. I have been an avid reader ever since.
Nice stuff writen here, i visit this great site."Love Feedforward Techniques - Part 4 - Modeling and Control" yet again...
Thats a detailed and informative blog. In simple fact, although this really is my primary time of going to this website, i ought to confess that I've observed a excellent resource center. I can,t pay for to miss out on these pages. Regards and maintain up the excellent perform.Best wishes!
I stumbled upon your weblog and wanted to tell you that that I have genuinely enjoyed reading through your web site posts.Thanks for sharing this data ,I seriously delight in reading it.
Wow that just about sums everything up
Behind every great fortune there is a crime. Honore de Balzac (1799-1850)
Super article you have got here.